Select the right gauge for the job.
- Gauges read most accurately in the middle two thirds of the dial
- Accuracy rating is based on full-scale (1)
- Our gauges come with everything you need for set up
- 1/4" Brass Tee
- 1/4" Brass Nipple
- 1/4" Drain Cock
- Quick Disconnect Couplings - Male and Female
Gauge Selection Chart
| Anticipated PSI Readings |
Gauge Range |
Reads In |
Accuracy Rating (1) |
Commonly Used On |
1/2%
Item # |
1%
Item # |
| 8-23 |
0-30 |
1 PSI |
GK30D4 |
GK30 |
Pitotless Nozzles |
| 15-45 |
0-60 |
1 PSI |
GK60D4 |
GK60 |
Hose Monsters, Pitotless Nozzles |
| 25-75 |
0-100 |
1 PSI |
GK100D4 |
GK100 |
Hose Monsters, Pitotless Nozzles, Gauge Caps |
| 40-120 |
0-160 |
2 PSI |
GK160D4 |
|
Hose Monsters, Pitotless Nozzles, Gauge Caps |
| 60-150 |
0-200 |
2 PSI |
GK200D4 |
|
Gauge Caps, Pump Discharge |
| 75-225 |
0-300 |
5 PSI |
GK300D4 |
|
Pump Discharge |
| Compound gauges for pump suction folllow the same rules but minimum is 30"Hg. The above gauges are normally in stock. Special gauges available upon request. |
| (1) ASME B40.1 Grade 2A (1/2%) or Grade 1A (1%) |
Gauge Selection Notes
Some manufacturers rate the accuracy of gauges at 2-1-2. This means 2% for the first third, 1% for the middle two-thirds and 2% for the last third.
Example #1: A zero to 100 PSI gauge would read 2% accuracy from 0-33, 1% from 34-66 and 2% from 67-100.
Our gauges are rated at 1/2% (or 1% if 2 1/2" dial) of full scale.
Example #2: A zero to 100 PSI gauge, 1/2% accuracy rated, would read within 0.5 PSI accuracy at both 10 PSI and at 90 PSI.
Example #3: A zero to 60 PSI gauge, 1/2% accuracy rated, would read within 0.3 PSI accuracy at both 10 PSI and at 50 PSI.
For best accuracy it makes sense to use a gauge with a smallest range. If gauge readings are anticipated to be around 30 PSI all the time, it would be better to use a 0-60 PSI gauge than a 0-100. The demarcation increments are wider and easier to read with the smaller range gauge.
Protective Gauge Boots for 4" and 2 1/2" diameter gauges
Protect your gauges against shock, impacts and corrosion. Boot si sold separately from gauge. Install it on gauge by hand.
Certified Gauges
Need certification? We offer dead-weight testing and traceable NIST certificates for an additional fee.

|